1.4.4.4.2 Legends for all devices on all diagrams.
1.4.4.4.3 Sequence of operation explanations for all
portions of all schematic wiring diagrams.
1.4.5 Engine/Generator Unit and Weatherproof Enclosure: Dimensional
data shall be given for the Engine/Generator set and for the
weatherproof enclosure.
a. Weight of skid mounted unit
b. Overall length
c. Overall width
d. Overall height
e. Exhaust pipe size
f. CFM of air required for combustion and ventilation
g. Heat rejected to jacket water and lubricating oil
BTU/hr.
h. Heat rejected to room by engine and generator
BTU/hr.
i. Weatherproof enclosure details and certification of
manufacturing method per specifications.
j. Base fuel tank, venting fuel connection points and fill cap
location
k. Data on all miscellaneous items supplied.
1.4.6 Optional System Service Contract
a. Equipment Supplier Company
Name
Address
City/State
Phone Number
b. Attach the number of copies required of System Service Contract
to submittal
1.4.7 Furnish the number of copies required of the MANUFACTURER’s
certified shop test record of each complete engine driven generator
unit.
1.4.8 Warranty information
1.4.9 Submit to the ENGINEER operating and maintenance data.
1.4.10 Submit to the ENGINEER the equipment MANUFACTURER’s
Certificate of Installation, Testing and Instruction.