2.4.5.1 Voltage Regulator:
2.4.5.1.1 The generator MANUFACTURER shall
furnish a hermetically sealed, silicon
controlled rectifier type voltage regulator
employing a zener reference with a +1
regulation for the generator. The
regulator shall include a 3-phase voltage
sensing, automatic short circuit
protection and shall include automatic
under-frequency protection to allow the
generator to operate at no load less
than synchronous speed for engine
start-up and shutdown procedures.
Switches and/or fused shall not be used
to provide this protection. An over-
voltage sensing module with manual
reset shall be furnished with the
regulator. A volts per Hz., sensing
module shall be provided as part of the
regulation system.
2.4.5.1.2 A voltage adjustment rheostat for 5
percent voltage adjustment on the unit
shall be provided.
2.4.5.1.3 High voltage step-down potential
transformers shall be provided for the
voltage regulator power input and
sensing circuits if required.
2.4.5.2 Sustained Short Circuit: A permanent magnetic
exciter shall be provided on the unit for
sustaining a current of 300 percent during a
short circuit, permitting the generator breaker
to trip on overload. To prevent possible
overheating of the armature windings,
appropriate relaying shall be supplied to limit
the fault to ten seconds. All current
transformers required shall be supplied by the
switch gear MANUFACTURER.
DIESEL ENGINE DRIVEN GENERATOR WITH WEATHERPROOF ENCLOSURE 472-13